6.0 Network Service

This is a 120/208 volt or 347/600 volt service located in the network area with the transformer connected to EDTI’s network system. The network area extends from 97 to 110 Street and from 97 to 104A Avenue in downtown Edmonton. Typical installations include medium to large commercial applications.

Table 1F

​Commercial Service Limits Residential Service Limits

120/240 V, 1 Ph, 3 W – N/A
240 V, 3 Ph, 3 W – N/A
120/208 V, 3 Ph 4 W – 3,000 A
120/208 V, 2 Ph, 3 W – 100 A
347/600 V, 3 Ph, 4 W – 1,600 A

Please contact EDTI for confirmation of the network voltage available in your area.

120/240 V, 1 Ph, 3 W – N/A
120/208 V, 2 Ph, 3 W – 100 A

Please contact EDTI for confirmation of the network voltage available in your area.

​​Customer's Responsibilities

  • Complete civil work on private property. This typically includes all trenching and ducts.
  • Install Current Transformers and Potential Transformers.

NOTE: The customer owns and maintains all secondary ducts on private property.

​EDTI's Responsibilities

  • Complete all work on public property.
  • Supply and install secondary conductors and make the final connection at the transformer or ring bus and the customer's switchgear.
  • Supply Current Transformers and Potential Transformers.
  • Supply and install revenue metering equipment.

NOTE: EDTI owns and maintains the secondary cable to the line side of the switchgear and revenue metering equipment.

Service Connection Point (Service Entry Point)

Property line.

​Point of Service Termination (Electrical Connection Point)

Switchgear.

6.1